How to handle Grid Neutral Line Lost issue for HSNV series inverter

How to handle Grid Neutral Line Lost issue for HSNV series inverter


Purpose:

When hopeCloud reports “Grid neutral line lost” alarm, this document can help to guide you on how to handle it.

1Fault cause

1.1 Poor connection of grid neutral line.

1.2 The inverter is not connected to nominal grid.

2. Troubleshooting Methods

Step 1

Login to hopeCloud APP, select the corresponding inverter and navigate Parameter Settings>System control> Reset command> 1-Reset. Then check whether the alarm persists. If the alarm is resolved after reset, the troubleshooting process is complete.



Step 2

If the issue persists, please check whether the grid neutral line is connected correctly. If not, please reconnect the grid neutral line cable.


Step 3

If the issue persists, login to hopeCloud APP to check whether the grid voltage is normal.

Normal grid voltage range:

380V: Line voltage range of 285~456V AC

 400V: Line voltage range of 300~480V AC

 

Step 4

If the voltage is within the normal range but the issue persists, please check the grid phase sequence is correct or not.

If everything appears to be in order but the issue continues, please contact Hopewind after-sales service for further assistance.


    • Related Articles

    • How to handle Emergency Stop issue for HSNV series inverter

      Purpose: When hopeCloud reports “Emergency stop” alarm, this document helps to guide you on how to check it. 1.Fault cause 1.1 External emergency stop switch closed. 1.2 Incorrect cable connection of inverter-side emergency stop switch. 2. ...
    • How to handle Parameter Back to Default Value issue for HSNV series inverter

      Purpose: When hopeCloud reports “Parameter back to default value” alarm, this document helps to guide you on how to handle it. 1.Fault cause 1.1 Wrong setting on hopeCloud. 1.2 Inverter internal component fault. 2. Troubleshooting Methods Step 1 Log ...
    • How to handle DC-side Startup Power Insufficient issue for HSNV series inverter

      Purpose: When hopeCloud reports “DC-side startup power insufficient” alarm, this document can help to guide you on how to handle it. 1.Fault cause 1.1 Insufficient illumination. 1.2 Lack of output on DC side. 2. Troubleshooting Methods Step 1 Log ...
    • How to handle FPGA Version Mismatch issue for HSNV series inverter

      Purpose: When hopeCloud reports “FPGA version mismatch” alarm, this document can help to guide you on how to handle it. 1.Fault cause 1.1 Mismatch between FPGA software version and the inverter. 1.2 Lack of output on DC side. 2. Troubleshooting ...
    • FAQ FOR HOPEWIND PV INVERTER

      Fault name Fault explanation Troubleshooting Grid abnormal Grid frequency/voltage/phase sequence exceed the parameter range 1. Check whether the AC circuit breaker is tripped. If it is tripped, switch on the AC circuit breaker. 2. Check if the AC ...