1. Purpose:
After completing the
power plant setup and configuring the Datalogger’s (hopePowerBox/hopeComBox)
WiFi network, if the hopeCloud shows that the inverter has not been detected,
this document will guide you through the process of checking and resolving the
issue.
This hopeCloud displays
no inverter detected.
3.1 Software version of the Datalogger is not the latest.
3.2 RS485 cable connection is incorrect.
3.3
Datalogger Baud rate setting of port2/3 is incorrect.
4. Checking steps and solution:
4.1 Datalogger software version should be 102.015.000 or higher; If not, update the software.
4.2 If the issue persists, verify the RS485 cable connection by referring to the installation manual.
4.3 If the issue persists, check the “Parameter settings” of the Datalogger, find the “Device topology information” and select “Port2/3 Baud rate”, set it to Baud rate “1-9600”.